RLGB-M/M-1050

RLGB-M/M-1050 is an electronic Modular Dual fuel burner with 1:10 turn down ratio, which is appropriate of different industrial aaplications. The values of CO and NOx during burner operation are lower than 30 and 120 mg/kWh; respectively, therefore, the burner’s NOx class of II is reported and approved.

Categories
  • Description

    RLGB-M/M-1050 Burner Equipments

    RLGB-M/M-1050 Burner Specifications

    Value Unit Model Manufacturer
    Minimum Gas Rated Output 1000 kW Main Motor 21 kW-Frame 180L ABB
    Maximum Gas Rated Output 10500 kW Pump Motor 2.2 Kw-Frame90 L IM(ITALMOTORS)
    Minimum Light Oil Rated Output 2000 kW Pump T3C 107 Suntec
    Maximum Light Oil Rated Output 10500 kW Control Box BT340 LAMTEC
    Minimum Gas Flow Rate 98 m3/h Main Gas Valve MVDLE 2080/5 Dungs
    Maximum Gas Flow Rate 1029.4 m3/h Safety Gas Valve MVD 2080/5 Dungs
    Gas Line Pressure 150 mbar Air Pressure Switch DG6U-3Z,DG50U-3Z Krom schroder
    Input Gas Pipe Size DN 80 in Gas Pressure Switch GW150-A5 Krom schroder
    Electric Power Supply Phase 3
    Electric Power Supply Frequency 50 Hz
    Electric Power Supply Voltage 400 V
    Fan Electrical Motor Power 21 kW
    Pump Electrical Motor Power 2.2 kW
    Fan Motor Speed 2900 rpm
    Pump Motor Speed 2720 rpm
    Operation Mode Modular
    Air Damper Automatic
    Centrifugal Fan (Backward, CCW) 590 x 160 x 48 mm
    Weight 400 kg