RLGB-M/M-1050
RLGB-M/M-1050 is an electronic Modular Dual fuel burner with 1:10 turn down ratio, which is appropriate of different industrial aaplications. The values of CO and NOx during burner operation are lower than 30 and 120 mg/kWh; respectively, therefore, the burner’s NOx class of II is reported and approved.
-
Description
RLGB-M/M-1050 Burner Equipments
RLGB-M/M-1050 Burner Specifications
Value Unit Model Manufacturer Minimum Gas Rated Output 1000 kW Main Motor 21 kW-Frame 180L ABB Maximum Gas Rated Output 10500 kW Pump Motor 2.2 Kw-Frame90 L IM(ITALMOTORS) Minimum Light Oil Rated Output 2000 kW Pump T3C 107 Suntec Maximum Light Oil Rated Output 10500 kW Control Box BT340 LAMTEC Minimum Gas Flow Rate 98 m3/h Main Gas Valve MVDLE 2080/5 Dungs Maximum Gas Flow Rate 1029.4 m3/h Safety Gas Valve MVD 2080/5 Dungs Gas Line Pressure 150 mbar Air Pressure Switch DG6U-3Z,DG50U-3Z Krom schroder Input Gas Pipe Size DN 80 in Gas Pressure Switch GW150-A5 Krom schroder Electric Power Supply Phase 3 — Electric Power Supply Frequency 50 Hz Electric Power Supply Voltage 400 V Fan Electrical Motor Power 21 kW Pump Electrical Motor Power 2.2 kW Fan Motor Speed 2900 rpm Pump Motor Speed 2720 rpm Operation Mode Modular — Air Damper Automatic — Centrifugal Fan (Backward, CCW) 590 x 160 x 48 mm Weight 400 kg