RLGB-M-205/LN

RLGB-M-205 is a single-stage gas burner designed for a wide range of domestic and industrial applications.This burner covers a firing range from 160 to 580 KW and is suitable for hot water boilers, steam boilers or air heaters. The burner is specially engineered to improve boiler’s performance in order to decrease fuel costs and emissions.

Categories
  • Description

    RLGB-M-205/LN Burner Equipments

    RLGB-M-205/LN Burner Specifications

    Value Unit Model Manufacturer
    Minimum Gas Rated Output 450 kW Main Motor 5.5 kW-MT1100LC/2 IM(ITALMOTORS)
    Maximum Gas Rated Output 2200 kW Pump Motor 550 W-GL 712-2-B34 GL LOHER
    Minimum Light Oil Rated Output 44 kg/h Pump AJ6CC SUNTEC
    Maximum Light Oil Rated Output 173 kg/h Control Box BT340 LAMTEC
    Minimum Gas Flow Rate 32 m3/h Main Gas Valve MVDLE 420/5 Dungs
    Maximum Gas Flow Rate 177 m3/h Safety Gas Valve MVD 220/5 Dungs
    Gas Line Pressure 74 mbar Air Pressure Switch DG6U-3Z Krom schroder
    Input Gas Pipe Size 2 in Gas Pressure Switch DG50U-3Z Krom schroder
    Electric Power Supply Phase 3
    Electric Power Supply Frequency 50 Hz
    Electric Power Supply Voltage 220 V
    Fan Electrical Motor Power 5.5 kW
    Fan Motor Speed 2850 rpm
    Pump Motor Power 1.1 kW
    Operation Mode Modular
    Air Damper Automatic
    Centrifugal Fan (Forward, CCW) 360 x 66 x 28 mm
    Weight 100 kg