RLGB-145

RLGB-145 is a two stage Dual fuel burner, designed for a wide range of domestic and industrial applications. The values of CO and NOx during burner operation are lower than 30 and 120 mg/kWh; respectively, therefore, the burner’s NOx class of II is reported and approved.

Categories
  • Description

    RLGB-145 Burner Equipments

    RLGB-145 Burner Specifications

    Value Unit Model Manufacturer
    Minimum Gas Rated Output 450 kW Main Motor 2.2 kW-Frame 90L-B5 SIEMENS
    Maximum Gas Rated Output 1380 kW Pump Motor 550 W-GL 712-2-B34 GL LOHER
    Minimum Light Oil Rated Output 39 kg/h Pump AJ6CC Suntec
    Maximum Light Oil Rated Output 118 kg/h Control Box LFL1.635/1.333 SIEMENS
    Minimum Gas Flow Rate 44.1 m3/h Main Gas Valve ZRDLE 420/5 Dungs
    Maximum Gas Flow Rate 135.3 m3/h Safety Gas Valve MVD 220/5 Dungs
    Gas Line Pressure 64 mbar Air Pressure Switch DG6U-3Z Krom schroder
    Input Gas Pipe Size 2 in Gas Pressure Switch DG50U-3Z Krom schroder
    Electric Power Supply Phase 3
    Electric Power Supply Frequency 50 Hz
    Electric Power Supply Voltage 220 V
    Fan Electrical Motor Power 2.2 kW
    Pump Electrical Motor Power 0.5 kW
    Fan Motor Speed 2850 rpm
    Pump Motor Speed 2850 rpm
    Stages 2
    Air Damper Automatic
    Centrifugal Fan (Backward, CCW) 387 x 80 x 24 mm
    Weight 73 kg